RLC Load Bank Manufacturer in Coimbatore, Tamil Nadu
Akshayam Controls & Automation designs and manufactures RLC load banks — resistive, inductive and capacitive elements combined in one unit — for testing generators, UPS systems and switchgear at realistic power factor. A purely resistive bank proves kW output and exercises the engine. It does not load the alternator field, and it tells you nothing about how the machine behaves when the site load is motor-heavy. An RLC unit adds lagging kVAR through iron-core reactors and leading kVAR through capacitor banks, so the set can be run at its full kVA rating and its true nameplate condition.
Each of the three sections is switched independently from the panel front, which means any kW and kVAR combination inside the unit rating can be set and held — typically 0.8 lagging for generator acceptance, unity for engine and cooling checks, and leading for UPS and inverter work where capacitive input filters and long cable runs push the power factor the other way. Over-temperature, airflow proving and capacitor discharge protection are built into every unit. Switchgear comes from Schneider Electric, L&T, Siemens, C&S Electric and ABB.
We are based in Coimbatore, and RLC enquiries reach us from a noticeably different map than our panel work — Kerala and Karnataka are as strong as Tamil Nadu, with Bengaluru the single busiest city. Units go to generator OEMs, third-party testing agencies, data centre commissioning teams and EPC contractors. Customers often pair the RLC unit with a Resistive Load Bank for straightforward kW trials, or order it alongside the DG Synchronization Panels it will be used to commission.
What is an RLC Load Bank?
An RLC load bank is a test load containing three element types in one enclosure: resistive banks that draw real power in kW, inductive reactors that draw lagging reactive power in kVAR, and capacitor banks that draw leading kVAR. Switching them in combination lets the operator present the source with a load of any chosen power factor. Because a generator is rated in kVA at a stated power factor — almost always 0.8 lagging — an RLC bank is the only way to load it to its actual nameplate figure and confirm the alternator, excitation system and AVR perform as specified.
Resistive Section (R)
Alloy elements draw real power at unity power factor, loading the engine, governor and cooling system in kW.
Inductive Section (L)
Iron-core reactors draw lagging kVAR, loading the alternator field and testing excitation and voltage regulation.
Capacitive Section (C)
Capacitor banks draw leading kVAR, reproducing UPS input filters, lightly loaded cables and inverter-fed systems.
Combined Power Factor Control
The three sections switch independently, so any point from 0.8 lagging through unity to leading can be set and held.
Key Features of Our RLC Load Banks
Independent R, L and C Switching
Separate step control for each section, so kW and kVAR are set independently rather than locked to a fixed power factor.
0.8 Lagging to Leading Range
Full sweep from 0.8 lagging through unity into leading power factor, covering generator acceptance and UPS testing on one unit.
Iron-Core Reactors
Air-cooled iron-core reactors sized for continuous duty, with tapped windings for stepped kVAR selection.
Capacitor Bank with Discharge
Capacitor sections fitted with bleed resistors that discharge the bank safely before the enclosure can be opened.
Full kVA and Power Factor Metering
Digital multifunction meter showing voltage, current, kW, kVAR, kVA, power factor, frequency and kWh together on the panel front.
Alloy Resistive Section
Fe-Cr-Al alloy helical coil and grid elements on ceramic insulators, matched to the reactive sections for balanced loading.
Protection & Interlocks
Over-temperature thermostat, airflow proving and fan-failure interlock, capacitor discharge circuit, MCB per bank and door interlock.
Local and PLC Control
Step switches and indication on the panel front, with PLC and HMI control offering power factor setpoint entry and automated load ramping.
Portable or Fixed Build
Trolley-mounted portable frames for testing agencies, floor-standing indoor units, weatherproof outdoor enclosures and container-mounted builds.
RLC Load Bank Applications
Why Choose Akshayam Controls for RLC Load Banks?
kW and kVAR Sized Together
The reactive split is worked out from the kVA and power factor you actually need to test at.
Full-Load Run Tested
Every unit run at rated kVA in our works, with power factor setpoints verified before dispatch.
All Three Sections In-House
Resistive, inductive and capacitive banks built and matched under one roof.
Built by Panel Engineers
Control and switching by our LT panel team, on Schneider, L&T, Siemens, C&S and ABB switchgear.
Coimbatore Works, Supply Across India
Built at Peelamedu, Coimbatore. Dispatched to Chennai, Bangalore, Kerala and nationwide.
Commissioning Support
Guidance on test procedure, kVAR staging and reading the results.
Our RLC Load Bank Manufacturing Process
Requirement Study
Source kVA, test voltage and frequency, power factor range, step resolution, duty cycle and installation type.
Electrical Design
Element, reactor and capacitor bank layout, step scheme, cooling airflow path and general arrangement drawing for approval.
Component Selection
Resistor elements, reactors, capacitors, contactors, fans and metering selected to the approved make list.
Fabrication & Assembly
Frame and enclosure fabrication, powder coating, element and reactor mounting, high-temperature wiring, control panel build.
Inspection & Full-Load Test
Insulation resistance, HV withstand, per-section step verification, discharge and interlock checks, full kVA thermal run.
Delivery & Support
Dispatched with drawings, test report and operating manual, with commissioning guidance where required.
Benefits of RLC Load Bank Testing
- Loads the generator to its true nameplate kVA, not just its kW
- Tests the alternator excitation system and AVR under reactive load
- Verifies voltage regulation when reactive load is applied and removed
- Reproduces motor-heavy site conditions before the plant depends on the set
- Satisfies OEM and consultant specifications that call for 0.8 PF testing
- Validates UPS performance at rated power factor rather than unity
- Leading power factor testing for inverter and capacitive-filter systems
- One unit covers kW-only, lagging and leading tests
- Documented kVA and power factor results for handover and approvals
- Independent kW and kVAR control supports staged commissioning procedures
Note: Test results reflect performance at the time of test. Continued reliability depends on fuel quality, battery condition and routine maintenance.
RLC Load Bank Specifications
| Parameter | Specification Details |
|---|---|
| Product Type | RLC Load Bank — combined resistive, inductive and capacitive |
| Load Type | Resistive kW, inductive lagging kVAR and capacitive leading kVAR, switched independently |
| Power Factor Range | 0.8 lagging, through unity, to 0.8 leading |
| Capacity Range | 25 kVA to 1000 kVA per unit; higher ratings by paralleling multiple units |
| Resistive Section | 20 kW to 800 kW |
| Inductive Section | 15 kVAR to 600 kVAR lagging |
| Capacitive Section | 10 kVAR to 300 kVAR leading |
| Test Voltage | 415 V, 3-phase, 4-wire, 50 Hz standard; 240 V single-phase and 60 Hz builds available |
| Load Steps | 1 kW, 5 kW, 10 kW and 25 kW resistive; 5 kVAR, 10 kVAR and 25 kVAR reactive |
| Resistive Elements | Fe-Cr-Al alloy helical coil and grid elements on ceramic insulators, continuous-duty rated |
| Reactive Elements | Air-cooled iron-core reactors with tapped windings; capacitor banks with bleed discharge resistors |
| Cooling | Forced air — axial fan array with ducted airflow and top or side hot-air discharge |
| Control | Independent R, L and C step switches on the panel front; PLC and HMI control with power factor setpoint and automated ramping |
| Metering | Digital multifunction meter — voltage, current, kW, kVAR, kVA, power factor, frequency and kWh |
| Protection | Over-temperature thermostat, airflow proving and fan-fail interlock, capacitor discharge circuit, MCB per bank, door interlock |
| Switchgear Make | Schneider Electric, L&T, Siemens, C&S Electric, ABB |
| Enclosure | CRCA sheet steel, seven-tank pre-treatment and powder coated — IP42 indoor, IP54 weatherproof outdoor |
| Configuration | Floor-standing indoor, weatherproof outdoor, trolley-mounted portable, or container-mounted |
| Cable Entry | Bottom entry with brass gland plate; camlock connectors or busbar terminals |
| Testing | Insulation resistance, HV withstand at 2.5 kV, per-section step verification, power factor setpoint check, full kVA thermal run |
| Reference Standards | ISO 8528-6 generator acceptance testing; IEC 62040-3 UPS testing; control section built to IEC 61439 |
RLC Load Bank Manufacturer Serving Chennai, Bangalore and Across India
RLC work takes us further afield than our panel business, and the buyer profile is different too — generator OEMs running type tests, third-party commissioning agencies, data centre contractors and test laboratories, rather than plant maintenance teams. Bangalore is our single busiest city for reactive load bank enquiries, followed by Chennai and a strong run of Kerala demand through Kochi, Kozhikode and Thiruvananthapuram. We also supply Hyderabad, Pune, Jaipur and the Delhi NCR belt. Every unit is designed, assembled and run at full kVA in Peelamedu, Coimbatore, and dispatched with drawings, test report and operating manual.
Frequently Asked Questions About RLC Load Banks
What is an RLC load bank?
An RLC load bank contains resistive, inductive and capacitive elements in one enclosure. The resistive section draws real power in kW, the inductive section draws lagging kVAR through iron-core reactors, and the capacitive section draws leading kVAR. Switching them in combination lets the operator load a generator or UPS at any chosen power factor instead of only at unity.
What is the difference between an RLC load bank and a resistive load bank?
A resistive load bank loads the source at power factor 1.0. It proves kW output and exercises the engine, governor and cooling system, which covers most routine generator testing. An RLC load bank adds reactive load, so the alternator field, excitation system and AVR are tested as well and the set can be run at its full kVA nameplate rating. If your specification calls for testing at 0.8 power factor, you need an RLC unit.
Why is generator testing done at 0.8 power factor?
Because that is how generators are rated. A set described as 500 kVA is 500 kVA at 0.8 lagging — 400 kW plus 300 kVAR. Loading it with 400 kW of pure resistance proves the engine but leaves the alternator running well under its design condition. Only reactive load brings the excitation system up to its rated point, which is where voltage regulation problems actually show up.
What is the capacitive section used for?
Leading power factor testing. UPS systems with capacitive input filters, inverter-fed and solar hybrid installations, and lightly loaded long cable runs all present a leading load, and generators behave differently under it — voltage can rise rather than sag. The capacitor section reproduces that condition so it can be checked before commissioning.
What capacity RLC load banks do you manufacture?
From 25 kVA units for UPS and small standby work up to 1000 kVA for large generator testing, with higher ratings achieved by paralleling units. The kW and kVAR split is set to the power factor range you need — a unit built for 0.8 lagging testing carries roughly three kVAR of reactive capacity for every four kW of resistive.
Do you manufacture inductive and capacitive load banks separately?
Yes. Where only reactive loading is needed — adding lagging kVAR to an existing resistive bank, for example — we build standalone inductive load banks and capacitive load banks. Many customers find the combined RLC unit better value once both are required, since one enclosure, one control panel and one cooling system serve all three sections.
Are you an RLC load bank manufacturer in Chennai and Bangalore?
We manufacture at our works in Peelamedu, Coimbatore, and supply RLC load banks regularly to Chennai and Bangalore — Bangalore is in fact our single busiest city for reactive load bank enquiries. We also supply Kochi, Kozhikode, Thiruvananthapuram, Hyderabad, Pune and the Delhi NCR region. Delivery, installation guidance and commissioning support are available in all of these locations.
How is the capacitor section made safe?
Each capacitor bank carries bleed discharge resistors that bring the stored charge down to a safe level once the section is switched out, and the enclosure is fitted with a door interlock so the bank cannot be opened while energised. Warning labels and a discharge time are marked at the access point.
How can I request an RLC load bank quotation?
Send the kVA rating of the generator or UPS to be tested, the power factor range you need to cover, the test voltage and frequency, your preferred step resolution, and whether the unit will be indoor, outdoor or portable. Email sales@akshayamcontrols.co.in or call +91 89403 32552 and our engineers will size the unit and quote.
Need an RLC Load Bank for Full kVA Testing?
Tell us the kVA rating and the power factor range you need to test at, and our engineers will work out the kW and kVAR split, share the drawing for approval, and build a unit that is run at full load before it leaves our works.
Phone: +91 89403 32552
Email: sales@akshayamcontrols.co.in